Caident Docs

Troubleshooting

Sign-in and startup

SymptomCause & fix
"You can verify your email on the Caident web app…"The account's email isn't verified. Use Open Caident web app, verify, then sign in again.
Access required screen after signing inYour current organization has no Caident Design license. Switch organizations (dropdown on that screen) or contact your admin.
Access screen mentions the device limitThe org's seats are full. Manage devices opens your device list on the web app — remove one, then retry.
Pipe Table Unavailable instead of HomeThe pipe catalogue couldn't load — no server and no local copy in C:\CaidentDesign or C:\CaidentCalc. Check the connection, restart the app.
App closes and reopens by itself right after launchThat's the silent auto-updater installing a new version. Normal.

Import and room detection

SymptomCause & fix
"Scanned PDFs aren't supported yet for automatic wall detection — imported as an image instead."The scan yielded nothing extractable. The plan is a picture: calibrate the scale, then draw rooms with Compartment / Lasso and walls with Barrier where routing needs them.
Rooms merged together or split oddlyWrong wall/door layer roles. Layers panel → Background section → set each layer's — / Wall / Door role; detection re-runs.
Rooms didn't detect at all on a DXFThe file had no units ($INSUNITS), so detection waits for scale. Background Options → Set background scale…, calibrate, done.
Dimensions or text from the drawing clutter the planLayers panel → Annotations row → Dimmed or Hidden. Or hide the whole PDF Underlay chip if detected text doubles the PDF's baked text.
Detected scale is wrong (walls 40 ft long)The sheet's scale text wasn't readable. Calibrate against a known distance — a 3-ft door opening works.
A room I edited keeps its old shape after re-detectionBy design: manually edited compartments are never regenerated. Select it and use Reset to auto-detected to hand it back.

Placement and routing

SymptomCause & fix
"No rooms detected. Make sure the background has enclosed wall geometry."Auto-place found no compartments — detection hasn't run (scale? roles?) or the space genuinely has no enclosed rooms.
Auto-place sprinklered a garage / skipped nothingSkip rules match room labels on the drawing. No "GARAGE" text → ordinary room. Review the placement report.
Can't place a device — nothing happens on clickDevices must land inside a space's region. Check you're clicking inside the active space (inactive spaces are faded).
Routed pipe crosses a wall it shouldn'tRouting only avoids barriers, not background walls. Draw a Barrier along the wall.
Routing ignores my boundaryThe boundary doesn't contain the space's sprinklers, so it's dropped. Redraw it around the heads.
A deleted routed span comes back after re-routeThe router re-grows what the tree needs. Draw the run you want as a manual pipe — that pins it.
Vertical Pipe tool is disabledNeeds 2+ spaces and the pair aligned — the tooltip says which is missing. Edit → Align spaces… first.

Hydraulics

SymptomCause & fix
"Cannot calculate yet:" with a listThe model is missing what's listed — sprinklers, riser, source, a connected network, or Static (psi) on the source.
"Please sign in before running Quick Calc."Quick Calc runs on the server and needs your session — sign in.
Quick Calc times out / "issue connecting to the calculation server"Network problem between you and the Caident server. (Despite the message's wording, CaidentCalc does not need to be running for Quick Calc.)
"Failed to send — is CaidentCalc running?"The Send buttons need CaidentCalc open on this machine. Start it, then re-send.
"Design is out of sync with Calculation" bannerYou edited the design after sending it to Calc. Re-send when ready; dismiss the banner meanwhile.

Files and exports

SymptomCause & fix
"This file does not appear to be a valid Caident Design project file."The file isn't a .cdsn (or it's corrupt). Recover from a backup copy.
Export DXF produced a .zipExpected: the plan has raster (scanned-PDF) backgrounds, which DXF can't embed — the ZIP holds the DXF plus one PNG per background.
A recent-projects row fails to openThe file moved or was deleted. Open it from its new location; the row updates on next save.

When something else is wrong

  • Undo (Ctrl+Z) reaches back 50 steps and covers everything, including imports and routing.
  • Most "operation failed" alerts carry the underlying message — note it before dismissing.
  • The ? menu shows the exact app version — include it when reporting a problem to Caident.